| Technical Specifications |
| Insulator type |
IEC |
|
U120B |
|
| GOST |
PS120ะ |
PS120ะ |
PS120ะ |
| Minimum mechanical failing load |
kN |
120 |
| Minimum mechanical residual strength |
kN |
96 |
| Diameter of the insulating part, D |
mm |
255 |
| Spacing, H |
mm |
127 |
146 |
170 |
| Nominal creepage distance |
mm |
320 |
| Ball and socket coupling, d (IEC 60120) |
mm |
16 |
| Puncture voltage in insulating medium |
kV |
130 |
| 50 Hz withstand voltage (dry) |
kV |
70 |
| 50 Hz withstand voltage (wet) |
kV |
45 |
| Dry lightning impulse withstand voltage 1.2/50 (+/-) |
kV |
100/100 |
| Impulse puncture test voltage in air |
kV |
280...310 |
| Radio interference voltage at 0.5 MHz |
dB |
60 |
| kV |
20 |
| dB |
86 |
| kV |
30 |
| Weight |
kg |
3.9 |
|
| All technical requirements and testing are in accordance with IEC standards. |